Global UPS Comparison Chart


Global UPS ETI's ETI0001-1241 Elgar's 2400A Acumetrics Rugged-UPS 3000
AC OUTPUT
Output voltage: UPS 120 VAC true sinewave standard, up to 600 VAC optional 115 VAC ±2% over full range of line and load variations 115 VAC ±5%
Output rating: UPS 3000 VA standard in 4U x 18.5" deep
0.65-0.75 pf standard, optional configurations to 24,000 VA
2400 VA into ±0.8 PF load 3000VA / 2400W
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating    
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
   
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds 150% for 30s; 150% to 200% for 3s  
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load 2% maximum THD with linear loads < 1% with 2000W load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
60 Hz ±0.1% 60 Hz ± 0.5 Hz
Operational status Status, load and battery LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off
   
AC INPUT
Input voltage selection: Nominal 115 VAC, optional autoranging input of 85-270 VAC 85 to 140 VAC or 170 to 280 VAC Single Phase 80-265 VAC, Single Phase
Input voltage tolerance: UPS 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load    
Input frequency: From 46 Hz to 70 Hz standard 45 to 450 Hz 47-440 Hz
Input power factor: Better than 99% typically   0.99 typical
Input/output isolation: 3000 VA, up to 120 dB common mode, <1.0 mA leakage    
Input transient suppression: Complies with IEEE 587 and UL 1449    
Input control/protection: Guarded 2 pole circuit breaker w/ fuse
Remote ON/OFF Control Interface
Optional cold start to turn on w/o AC present
  50A Circuit Breaker rated
Input power connection: MS 3102A-22-2P, 3 pin, threaded locking    
BATTERY EXTERNAL BATTERY INTERNAL BATTERY  
battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
192 VDC, 2.5 AH sealed lead acid Lithium-Ion or low maintenance RVLA
battery life: Rated for continuous service life of 5 years    
DC protection: Front panel mounted fuse standard, breaker optional    
battery time: 8+ minutes @ 100% load, 20+ minutes @ 50% 5 minutes for internal module with 2400 VA load, 0.8 PF @ 25°C.
Adding one external battery pack increases time to a
minimum of 18 minutes at full rated load. Reduced loads increase backup time.
8 minutes with Lithium-Ion
6 minutes with RVLA
External Battery: 30 min. withLithium-Ion
or 22 min. with VRLA
battery recharge: Recharged to nominal in <8 hours 4 hours, 90% full charge with integral battery charger 3 hours with Lithium-Ion
4 hours with VRLA
5 hours with External Battery
battery replacement: Drawout/plug-in module from front of unit 96 cells at 2.0 V, 2.5 AH in a single pullout, removable module  
DISTRIBUTION PANEL
Output circuits: One output standard, optional configurations Switches on or off the GUPS output  
Output control: Optional remote control panel w/rocker switches    
Output receptacles: MS 3102A-22-2S, 3 pin, threaded locking    
MECHANICAL
Dimensions (H x D x W): UPS
    2U Battery Module
7.0 (4U) x 18.5 x 19.0 in (178 x 470 x 483 mm)
3.5 (2U) x 18.5 x 19.0 in (89 x 470 x 483 mm)
7"H x 19"W x 25.1"L 7"H x 17"W x 21"L
Rack Slide Mount Patterns: Jonathan, General Devices patterns, others optional    
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical    
Unit weight: UPS w/o Battery
   2U Battery Module
95 lb. (43 kg) UPS Module with lift handles front and rear
102 lb. (46 kg) Battery Module with lift handles front and rear
78 lbs, maximum without battery module.
Removable internal battery module is 48 lbs (126 lbs max combined weight).
GUPS 2400A-104 variant (123 lbs max combined weight).
85 lbss without battery module
135 lbs.w lead acid battery
103 lbs. w lithium-ion battery
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale    
Cooling type: High capacity, positive pressure, forced air    
Cooling air direction: Rear intake, exhaust to front, others optional    
Air intake filter: Washable metal filter media, others optional    
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries non-operating -40° to 65°C -32° to 66°C (w/o batt: -40° to 70° C)
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional Operating 0° to 40°C -18° to 50°C (w/o batt: -30° to 65° C)
Operating humidity: 0 to 95% relative humidity (non-condensing) 5 to 95% non-condensing 5% to 95% (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m) non-operating 0 to 40,000 ft non-operating 0 to 40,000 ft
Operating elevation: Up to 15,000 ft (4,572 m), higher optional Operating 0 to 10,000 ft 0 to 15,000 ft
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
  MIL STDs 167-1, 810-G, 901D Grade A, 1399-300A
Canada: CSA C22.2 No. 107 UPS safety requirements    
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461   MIL STD-461-F, RE102, CE102, CS101, RS103,